[Beowulf] cooling question: cfm per rack?
Many of your questions may have already been answered in earlier discussions or in the FAQ. The search results page will indicate current discussions as well as past list serves, articles, and papers.
Mark Hahn hahn at physics.mcmaster.caFri Feb 11 21:41:41 PST 2005
- Previous message: [Beowulf] cooling question: cfm per rack?
- Next message: [Beowulf] cooling question: cfm per rack?
- Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]
> The second term really has two parts: > A. the amount of air moved > B. the reduction in temperature of that air across the A/C unit > > The latter part is specified in tons. The A/C guys I've spoken well, I usually think of temperature as a side-effect of the more direct measure, movement of energy. hence, I always think of the tidy relation of 3.517 KW = 1 ton. I usually skip any BTUs... > with recently utilize some more or less standard relationship > between cubic feet per minute (cfm) and A/C tons for the units they > maintain. CFM and delta-t across the machine-to-be-cooled are convolved to give you how much heat you're extracting. no doubt both pressure and humidity are involved to some degree as well, and I don't have a good equation for this. the good thing is that turning down the temperature can partly mitigate minor airflow problems. some reasonable discussion from Intel, (a bit axe-grinding, though): http://www.7x24nw.org/Presentations-folder/Air%20Cooling%20in%20Servers%20and%20IT%20Facilities.pdf a dell 1855 blade chassis spec's 400 CFM for ~4KW. they're talking 6 of those chassis in a rack (24 KW!). then again, that's assuming an unrealistic power-per blade (>400W), which sounds like corporate CYA to me: http://www.dell.com/downloads/global/products/pedge/en/PowerEdge%201855%20DC%20Whitepaper.pdf this is a good overall discussion, though perhaps a bit pessimistic about "typical" machinerooms: http://www.chatsworth.com/uploads/pdf/best_practices_cooling_wp.pdf http://www.chatsworth.com/uploads/pdf/increase_computerrm_cooling_wp.pdf sun recommends 21-23C, 45-50%. 35% min, ESD critical at 30%: http://www.sun.com/products-n-solutions/hardware/docs/html/817-4137-10/2__EnvReq.html to complicate matters, HVAC folk always bring up the issue of "sensible load". as near as I can tell, this is just a way of saying that if you try to impose too much delta-T on humid air, you wind up wasting a lot of energy dehumidifying it... tiles between 500-2000 CFM: http://h200005.www2.hp.com/bc/docs/support/SupportManual/c00064724/c00064724.pdf that also gives: CFM = btu/hr / (1.08 * dT) so for 1 ton = 12000 BTU/hr and 70->90, 555 CFM per ton of cooling. HVAC folk also tend to say 1 tile/ton, which seems about right. > These run off the campus cold water supply, so > it makes sense that heat out is proportional to flow across, assuming > that the cold water has a very large heat capacity. our experience with CW has been disasterous, but we made the huge mistake of not using precision/machineroom chillers (fancoils, actually). our old/existing machineroom, for instance, is supposed to have 2x8ton fancoils, but combined they never moved more than about 20 KW (should be 56). unless you have pretty extreme assurances about WC quality (flow, temp), I would only consider using dual-cool machineroom chillers (DX + CW, usually adds about 15% to price.) > directly through the A/C. Even more ideally cfm through _each_ rack > could be modulated somehow, since some racks move much more > air than others and putting a low flow rack next to a high flow rack > might drive the air the wrong way through the low flow unit. well, the stuff in racks does probably have quite a few fans, which could ideally modulate themselves. my current-gen clusters certainly don't do that, but I'd be quite happy if next-gen did... > How does one calculate an optimal cfm through a rack? > > For a specific example with round numbers, let's say it's a > 25U rack, dissipates 10kW, and has a single 50 cfm per minute output > fan per 1U node. (Ie, all air out must go through that path.) that sounds reasonable to me - 10KW is ~3 tons, and the formula above relates your 1250 CFM total to about 3 tons as well. for my 10KW racks, I'm hoping to push the temperature down a bit (60-65), keep the humidity low to avoid "sensible" wastage, and hope for the best with our tiles. > Is cfm the key unit here or should one think in terms of pressure > at various points in the room? I think the answer is yes. with a good raised floor, you seem to be able to expect fairly even pressure distribution. we turned on our new machineroom yesterday, and the pressure feels similar everywhere (16" raised floor, though with some conduits down there, and 3x30T Liebert deluxe system 3's.) if your pressure is reasonably even, the same tiles should flow the same CFM. I'd LOVE to find some way to measure airflow, since I'd actually consider doing things like adding patches of duct tape to the underside of too-high-flow tiles. I suppose that the empiricist approach is just to sample all your system temperatures, and if some are too high, reduce the airflow to racks which are "too cool".
- Previous message: [Beowulf] cooling question: cfm per rack?
- Next message: [Beowulf] cooling question: cfm per rack?
- Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]
More information about the Beowulf mailing list