Need ball park power and cooling requirements

Many of your questions may have already been answered in earlier discussions or in the FAQ. The search results page will indicate current discussions as well as past list serves, articles, and papers.

Search

Ben Ransom bransom at ucdavis.edu
Tue Oct 1 14:58:07 PDT 2002


At 03:34 PM 10/1/02 -0400, you wrote:
>On Tue, Oct 01, 2002 at 10:09:52AM -0700, Ben Ransom's all...
> > At 04:01 PM 9/30/02 -0600, Dean Johnson wrote:
> > >On Mon, 2002-09-30 at 15:17, Timothy H. Keitt wrote:
> > > > I'm setting up lab space and plan to build a small (8-16 node) cluster
> > > > of dual Xeon nodes (Dell 2650 or equivalent). I need to give the
> > > > engineers the power and cooling needed in the 6'x8' server room that
> > > > will house the cluster. Any rules-of-thumb for what's required? Thanks.
> > > >
> > >
> > >A good ballpark, with decent margins, would be 300w per box. You need to
> > >add things like monitors and switches too.
> > >
> > >         -Dean
> >
> > I'd add a little more margin.  I'm using dual athlons, which may be more
> > power thirsty than Xeons -- dunno. Nonetheless, planning on just the power
> > supply rating per box could be limiting.  Our cluster sometimes goes over
> > calculated amp (and power) ratings when all cpus are crunching 100%.  We
> > have Baytech power strips rated at 20 amps which should have handled 7 
> dual
> > athlon boxes apiece, if going by the spec numbers.  We had to add another
> > power strip and spread out to only 5 boxes each.  Fortunately, I had 
> enf 20
> > amp circuits in the room (4 for a 20 node cluster + eth switch + head 
> node).
>
>3.5 amps per machine? MPs on what board? how much ram and how many HDs?
>
>/kc

dual Athlon 1900MPs on Tyan 2466N, 1g Ram, 1 60gb atadrive each (pvfs), and 
wulfkit.
Ack, perhaps I misled things just a little in saying 5 boxes each.  I could 
do 6 each circuit, but the point was that 3 power strips was not enf for 
all 20 nodes, so I now spread the 20 nodes evenly across 4  20amp 
strips.  The Baytech power strips report peak amps.  I got readings of 19 
amps with 6 nodes plugged in and running 100%cpu.  I got over 21 amps with 
7 nodes plugged in, 100%cpu.  On this, the Baytechs didn't trip until over 
22amps, so I guess they throw in a little fudge factor in our favor.  On 
the other hand, the Baytechs were reporting  higher load than should be 
possible from the  power supplies.  I think these are PCF power supplies, 
but that is fuzzy memory now.  I think they are 300w which should be max of 
~2.75amps.  So, 6 boxes * 2.75 should be max draw of 16.4 amps, yet the 
Baytechs reported 19amp at 100% cpu utilization.
-Ben


> >
> >
> > -Ben Ransom
> >   Programmer/ Systems Administrator
> >   Mechanical & Aeronautical Engineering, UC Davis
> >   (530) 752-1834  Fax: 752-4158
> >
> > _______________________________________________
> > Beowulf mailing list, Beowulf at beowulf.org
> > To change your subscription (digest mode or unsubscribe) visit 
> http://www.beowulf.org/mailman/listinfo/beowulf
>
>--
>Ken Chase, math at velocet.ca  *  Velocet Communications Inc.  *  Toronto, 
>CANADA




More information about the Beowulf mailing list